High Pressure Safety


High Pressure control reset
Scotty McGregor
HVAC Oracle

 
2005-07-03  

Symptom: No Cooling, Indoor Fan Runs, Compressor Does not start Caused By:High Pressure Safety Control Tripped-Reset required


Encapuslated High Pressure Contrl


Not all AC units have high pressure protection. Most smaller residential units do not. This device protects the compressor if the condenser fan motor quits or the coil becomes plugged. The reset buttom is external on some units. Look for a small red button protruding from the side of the condensing unit casing. It may be located behind the compressor access panel. It is not normally locate in the eletrical control area, but some are. Make sure the power is off before removing any panel. Look for a control simaler to the pictures shown. If there is a high pressure control it pressure sensing line will be located on the discharge line off the compressor or on the liquid line from the condenser. The reset button can be mounted directly on the line, or it may be connected via a capillary tube into the control panel. This is reset switch will hold the compressor off until it is reset. After it is reset the compressor may or may no start right away, but you should feel or hear a click when it is reset.
After the compressor does start,locate the cause of the high pressure or it will just tripped of again. Repeated high pressure failure will burn out the compressor. Check the condenser coil, make sure it is clean, the condenser coil should be clean regularly. Check the condenser fan motor. If the motor is load or noisy then the bearings maybe worn out, the can cuase the condenser fan to shut down on an internal over load and then cause the high pressure control to trip off. Check fan blade or mountings, are they tight and the blade can rotate freely? Sometimes a high pressure failure happens when the system is overcharge with refrigerant. It will run OK warm days and trip off on really hot days when you need it the most.

Do not attemp to remove the high pressure control, this may cause the release of the refrigerant gas.





Air Conditioning Tips

Preventive Maintenance for portable or window air conditioners

Dirty condenser coils

Freezing evaporator

High Pressure Control Tripped

Keep your AC going in on the hottest day of the year.
Residential AC wiring Diagram

INSPECTION FORMS
CENTRAL AC
ECONOMIZERS
ROOFTOP AC
CHILLERS
PORTABLE

SERVICE TIPS
Live Technical Support
Need to talk to tech. Click here and complete payment to get live help

How to buy an Air Conditioner
I am often asked, " What brand of air conditioning would you recommend"

Split AC Inspection.
Level one inspection Check list for spring AC Start

AC Wire Diagram
Typical 4 wire diagram for a residential furnace/AC thermostat

Spring PM of Window/Portable unit
What maintenance is needed for portable or window ac units

Over Heated Wiring
Regularly inspect the wiring connections in AC equipment

High Pressure Safety Tripped
If your AC over heats it may shut down on high pressure

Frozen Evaporator
What causes the evaporator to freeze?

PM for Residential AC
Basic maintenace for your home AC

Dirty Condenser Coil
Annual cleaning of the condenser coil.