Carrier VVT Enhanced System Pre 1993
Monitor Thermostat Programming
Rotary
Position
|
Function
|
1
|
Device Address
|
2
|
Setback Override Time Limit
|
3
|
Setback Setpoints
|
4
|
Comfort Setpoint Limiting
|
5
|
Damper Max Open
Vent Poistion
Minimum Position
|
6
|
Zone Temperature Sensor
Calibration
|
7
|
Supply Air Temperature
Sensor Calibration
|
8
|
Airflow Sensor Error Correction
|
9
|
Air Flow Setpoint
|
A
|
Damper Size
|
B
|
System Mode Demand
|
C
|
Cooling Lockout Temperature
Setpoint
Heating Lockout Temperature Setpoint
|
D
|
Communication Check
|
F1
|
Timeguard override
|
F2
|
Local Setback Control
|
F3
|
Alternate Information Display
|
F4
|
Supplemental Heat Lockout
|
F5
|
Supplemental Heat Fan Relay
|
F6
|
Zone Pressure Independent
Operation
|
F7
|
CFM Calculation
|
F8
|
Celsius Temperature Display
|
F9
|
High Torque Actuator
|
F10
|
Clockwise Open Damper Modulation
|
F11
|
Error Code Display
|
F12
|
Setback Programming Lock
|
F13
|
Local Setback Override
|
F14
|
Meter Setback
|
F15
|
Meter HVAC
|
F16
|
Ventilation Mode
|
F17
|
2400 Baud Rate
|
F18
|
DX Coil Temperature Sensor
|
F19
|
Local Outside Air Temperature
Sensor
|
F20
|
Local Humidity Sensor
|
F21
|
High/Low Temperature Limits
|
F22
|
Secondary High/Low Limit
Temperaute Scale
|
F23
|
Heat Pump System
|
F24
|
Auto Fan off for Heat
|
F25
|
Temperature Trend Staging
|
F26
|
System Heating Mode Lockout
|
F27
|
Supplemental Heat Callers
|
F29
|
Multiple Zone System
|
F30
|
Monitor Only System
|
F31
|
W973 Economizer Control
|
F32
|
Time Guard Between Modes
|
Via Communications Only
|
Comfort Trend Demand Setpoint
Comfort Trend Time Limit
System Airflow Setpoint
System Mode Re-select
DX Coil Temperature Sensor Calibration
Local Outside Air Temperature Sensor Calibration
Device Security
Zone Usage Meter
Rotary Switch Lock
System Heating Mode Setpoint
System Cooling Mode Setpoint
|
Bypass Controller Rotary Function
Switch Position
|
Function
|
1
|
Device Address
|
2
|
Maximum Pressure Set point
|
3
|
Minimum Pressure Set Point
|
4
|
Change Over Setpoint
|
5
|
Damper Max & Min. Position
|
6
|
Bypass Controller Temp
Sensor Calibration
|
7
|
Supply Air Sensor Calibration
|
8
|
Pressure Sensor Calibration
|
9
|
Pressure Sensor Error Correction
|
A
|
Pressure Sensor Calibration
Times
|
B
|
Auto-Calibration Fan-Off
Delay
|
C
|
|
D
|
Zone Damper Control
|
E
|
Auto-Pressure Setpoint
|
F1
|
Change over Cycle
|
F2
|
VS Sensor
|
F3
|
2400 Baud Rate
|
F4
|
Celsius Temperature Display
|
F5
|
High Torque Actuator
|
F6
|
Clockwise Open Damper Modulation
|
F7
|
Stand Alone Operation
|
F8
|
Error Code Display
|
F9
|
Pre-Enhaced System Compatiblity
|
Communication PCCC Only
|
Device Security Code
Rotary Switch Lock
System Air Flow Setpoint
Miscellaneous Temperature Sensor Calibration
|
| |
|
Rotarty Switch
Position
|
Function
|
1
|
Device Address
|
2
|
Setback Override Time Limit
|
3
|
Setback Setpoints
|
4
|
Comfort Setpoint Limiting
|
5
|
Damper Max & Vent/Min Positions
|
6
|
Zone Temp. Sensor Calibration
|
7
|
Supply Air Temp. Sensor
Calibration
|
8
|
Airflow Sensor Error Correction
|
9
|
Airflow Setpoint
|
A
|
Damper Size
|
B
|
not used
|
C
|
Not Used
|
D
|
Not Used
|
E
|
Not Used
|
F
|
Multi Function See List
|
| |
|
F Position Functions
F-Number
|
Function
|
F-1
|
Suppl. Heat Timeguard Override
|
F-2
|
Local Setback Control
|
F-3
|
Alternate Information Display
|
F-4
|
Zone Supplemental Heat
|
F-5
|
Continous Fan Operation
|
F-6
|
Zone Press. Independent
Operation
|
F-7
|
CFM Calculation
|
F-8
|
Celsius Temperature Display
|
F-9
|
High Torque Actuator
|
F-10
|
Clockwise Open Damper Modulation
|
F-11
|
Error Code Display
|
F-12
|
Local Setback Override
Lock
|
F-13
|
Local Setback Override
Lock
|
F-14
|
Meter Setback Override
|
F-15
|
Meter HVAC
|
F-16
|
Ventilation Mode
|
F-17
|
2400 Baud Rate
|
F-18
|
PS Valve Box (SSP01-E)
|
SF Errors
SF Error
|
Information Affected
|
SF01
|
Device Address
|
SF02
|
Comfort Setpoints
|
SF03
|
Setback Setpoints
|
SF04
|
Damper Maxiumum Open Postion,
Damper Vent/Min Air flow Position
|
SF05
|
Suppl. Heat Damper Position
|
SF06
|
Comfort Setpoint Limiting
|
SF07
|
Does not Apply to Slave
Stat
|
SF08
|
System Options #1
Local Setback Control
Continuous Fan Operation
Zone Supplemental Heat-Alternate Information
Zone Pressure Indep. Ops
CFM Calculation
Celsius Temp. Display
|
SF09
|
System Options #2
High Torque Actuator
Clockwise Open Damper Modulation
Error Code Display-PS Valve Box (SSP01E)
|
SF10
|
Does not apply to Slave
Stat
|
SF11
|
System Options #3
Setback Programming Lock
Local Setback Override Lock
Meter Setback Override
Meter HVAC-Ventilation Mode
Rotary Switch Lock
|
SF12
|
Setback/Comfort Program
|
SF13
|
Zone Temperature Sensor
Calibration
|
SF14
|
Supply Air Temperature
Sensor Calibration
|
SF15
|
Airflow Sensor Error Cor.
(SS01E)
Pressure Sensor Comm. (SSP01E)
|
SF16
|
Airflow Setpoint
|
SF17
|
Setback Override
|
SF18
|
Comfort Trend Demand Setpoint
Comfort Trend Time Limit
|
SF19
|
Does not Apply to Slave
Stat
|
SF20
|
Does not Apply to Slave
Stat
|
SF21
|
Does not apply to Slave
Stat
|
SF22
|
PS Temp. Sensor Calibration
(SSP01E)
|
SF23
|
Airflow Sensor Error Cor.
(SSP01E)
|
SF24
|
Pressure Sensor Cal. (SSP01E)
|
SF25
|
Device Security Code
|
SF26
|
Does Not Apply to Slave
Stat
|
SF27
|
2400 Baud Rate
|
SF28
|
Zone Usage Meter
|
Hardware Failure Codes
HF Error
|
Hardware Problem
|
HF29
|
Can not detect open damper
|
HF30
|
Cannot detect Closed Damper
|
HF31
|
Zone Temperature Sensor
out of operating range
|
HF32
|
Supply Air Temperature
sensor out of operating range
|
HF33
|
Airflow Sensor out of operating
range
|
HF34
|
Does not apply to slave
stats
|
HF35 & HF36
|
Micro-electronic component
failure
|
|