Carrier VVT Enhanced System Pre 1993


Monitor Thermostat Programming

Rotary
Position
Function
1
Device Address
2
Setback Override Time Limit
3
Setback Setpoints
4
Comfort Setpoint Limiting
5
Damper Max Open
Vent Poistion
Minimum Position
6
Zone Temperature Sensor Calibration
7
Supply Air Temperature Sensor Calibration
8
Airflow Sensor Error Correction
9
Air Flow Setpoint
A
Damper Size
B
System Mode Demand
C
Cooling Lockout Temperature Setpoint
Heating Lockout Temperature Setpoint
D
Communication Check
F1
Timeguard override
F2
Local Setback Control
F3
Alternate Information Display
F4
Supplemental Heat Lockout
F5
Supplemental Heat Fan Relay
F6
Zone Pressure Independent Operation
F7
CFM Calculation
F8
Celsius Temperature Display
F9
High Torque Actuator
F10
Clockwise Open Damper Modulation
F11
Error Code Display
F12
Setback Programming Lock
F13
Local Setback Override
F14
Meter Setback
F15
Meter HVAC
F16
Ventilation Mode
F17
2400 Baud Rate
F18
DX Coil Temperature Sensor
F19
Local Outside Air Temperature Sensor
F20
Local Humidity Sensor
F21
High/Low Temperature Limits
F22
Secondary High/Low Limit Temperaute Scale
F23
Heat Pump System
F24
Auto Fan off for Heat
F25
Temperature Trend Staging
F26
System Heating Mode Lockout
F27
Supplemental Heat Callers
F29
Multiple Zone System
F30
Monitor Only System
F31
W973 Economizer Control
F32
Time Guard Between Modes
Via Communications Only
Comfort Trend Demand Setpoint
Comfort Trend Time Limit
System Airflow Setpoint
System Mode Re-select
DX Coil Temperature Sensor Calibration
Local Outside Air Temperature Sensor Calibration
Device Security
Zone Usage Meter
Rotary Switch Lock
System Heating Mode Setpoint
System Cooling Mode Setpoint

Bypass Controller Rotary Function

Switch Position
Function
1
Device Address
2
Maximum Pressure Set point
3
Minimum Pressure Set Point
4
Change Over Setpoint
5
Damper Max & Min. Position
6
Bypass Controller Temp Sensor Calibration
7
Supply Air Sensor Calibration
8
Pressure Sensor Calibration
9
Pressure Sensor Error Correction
A
Pressure Sensor Calibration Times
B
Auto-Calibration Fan-Off Delay
C
 
D
Zone Damper Control
E
Auto-Pressure Setpoint
F1
Change over Cycle
F2
VS Sensor
F3
2400 Baud Rate
F4
Celsius Temperature Display
F5
High Torque Actuator
F6
Clockwise Open Damper Modulation
F7
Stand Alone Operation
F8
Error Code Display
F9
Pre-Enhaced System Compatiblity
Communication PCCC Only
Device Security Code
Rotary Switch Lock
System Air Flow Setpoint
Miscellaneous Temperature Sensor Calibration
   

Rotarty Switch

Position
Function
1
Device Address
2
Setback Override Time Limit
3
Setback Setpoints
4
Comfort Setpoint Limiting
5
Damper Max & Vent/Min Positions
6
Zone Temp. Sensor Calibration
7
Supply Air Temp. Sensor Calibration
8
Airflow Sensor Error Correction
9
Airflow Setpoint
A
Damper Size
B
not used
C
Not Used
D
Not Used
E
Not Used
F
Multi Function See List
   

F Position Functions

F-Number
Function
F-1
Suppl. Heat Timeguard Override
F-2
Local Setback Control
F-3
Alternate Information Display
F-4
Zone Supplemental Heat
F-5
Continous Fan Operation
F-6
Zone Press. Independent Operation
F-7
CFM Calculation
F-8
Celsius Temperature Display
F-9
High Torque Actuator
F-10
Clockwise Open Damper Modulation
F-11
Error Code Display
F-12
Local Setback Override Lock
F-13
Local Setback Override Lock
F-14
Meter Setback Override
F-15
Meter HVAC
F-16
Ventilation Mode
F-17
2400 Baud Rate
F-18
PS Valve Box (SSP01-E)

SF Errors

SF Error
Information Affected
SF01
Device Address
SF02
Comfort Setpoints
SF03
Setback Setpoints
SF04
Damper Maxiumum Open Postion,
Damper Vent/Min Air flow Position
SF05
Suppl. Heat Damper Position
SF06
Comfort Setpoint Limiting
SF07
Does not Apply to Slave Stat
SF08
System Options #1
Local Setback Control
Continuous Fan Operation
Zone Supplemental Heat-Alternate Information
Zone Pressure Indep. Ops
CFM Calculation
Celsius Temp. Display
SF09
System Options #2
High Torque Actuator
Clockwise Open Damper Modulation
Error Code Display-PS Valve Box (SSP01E)
SF10
Does not apply to Slave Stat
SF11
System Options #3
Setback Programming Lock
Local Setback Override Lock
Meter Setback Override
Meter HVAC-Ventilation Mode
Rotary Switch Lock
SF12
Setback/Comfort Program
SF13
Zone Temperature Sensor Calibration
SF14
Supply Air Temperature Sensor Calibration
SF15
Airflow Sensor Error Cor. (SS01E)
Pressure Sensor Comm. (SSP01E)
SF16
Airflow Setpoint
SF17
Setback Override
SF18
Comfort Trend Demand Setpoint
Comfort Trend Time Limit
SF19
Does not Apply to Slave Stat
SF20
Does not Apply to Slave Stat
SF21
Does not apply to Slave Stat
SF22
PS Temp. Sensor Calibration (SSP01E)
SF23
Airflow Sensor Error Cor. (SSP01E)
SF24
Pressure Sensor Cal. (SSP01E)
SF25
Device Security Code
SF26
Does Not Apply to Slave Stat
SF27
2400 Baud Rate
SF28
Zone Usage Meter

Hardware Failure Codes

HF Error
Hardware Problem
HF29
Can not detect open damper
HF30
Cannot detect Closed Damper
HF31
Zone Temperature Sensor out of operating range
HF32
Supply Air Temperature sensor out of operating range
HF33
Airflow Sensor out of operating range
HF34
Does not apply to slave stats
HF35 & HF36
Micro-electronic component failure